New College Natatorium Becomes Student Social Hub Thanks to Comfortable IAQ
The drive-in movie might be quickly fading from
Western culture, but the dive-in movie is a floating
sensation at the new $27 million Student
Recreation Center’s natatorium at Appalachian
State University, Boone, N.C.
Students dive into the 24,000-square-foot
natatorium’s 50-meter pool and float while watching
a student film society movie on a wall purposely
kept blank for movie projection. The dive-in movie,
plus a submerged jetted therapy bench for sore
muscles and other student inputs solicited by the
center’s design committee have helped create a
unique indoor pool that seconds as a trendy social
hub.
While the Dive-In Movie and other student ideas
are a novel approach, it is the indoor air quality (IAQ) design of James Giles, vice president/project manager, and Atul
Nerurkar, P.E., vice president and senior design engineer, United Engineering Group, Charlotte, N.C., that makes these
unconventional natatorium functions comfortable experiences.
“These facilities are more than gyms or recreation space,” said Mark Zack, AIA, partner, Corley Redfoot Zack, a Chapel
Hill, N.C.-based architectural/engineering firm with similar facility designs at East Carolina University, UNC-Wilmington,
and Western Carolina University. “They are also social hubs of the campus to the extent they are surpassing the student
union as a gathering place.”
Because the recreational facility seconds as a social hub with a 24 hours/day occupied cycle on ASU’s 250-acre campus
built into the Blue Ridge Mountains, energy efficiency was a major HVAC design goal. Thus, heat recovery was a major
option in United’s dehumidifier performance specification. Custom manufactured by Dectron Inc., Roswell, Ga., the
dehumidifiers not only keep the center a comfortable 55 percent relative humidity (RH), but also save energy by
efficiently providing free pool water heating while simultaneously heating or cooling the space.
Besides free pool water heating, another energy measure the design team specified is an Econo-Saver powered
exhaust system option on the dehumidifiers that uses exhaust air heat transfer to pre-heat incoming outside air that is
approximately 25-percent of the natatorium’s total 56,900-cfm.
The DRY-O-TRON units’ onboard Supervisaire microprocessor controls the natatorium humidity, however a Johnson
Controls (CSP), Milwaukee, Wis., Metasys building automation system monitors/alarms the dehumidifier operation and
controls the center’s non-pool spaces such as the weight room, gym, rock climbing wall, and other areas.
Constructed by Shelco, Winston Salem, N.C., under the North Carolina State Construction Office’s CM@Risk program,
the project was packed with energy-saving equipment options outlined in the performance specification by United. The
energy-saving options custom manufactured into the equipment would not only provide a quick payback, but also save
the university hundreds of thousands of dollars in energy costs over the life of the equipment. Faulkner/ Haynes Inc., a
Raleigh, N.C.-based manufacturer’s representative acted as a liaison to ensure United’s performance specifications
were all met at the manufacturing level.
Besides energy efficiency, airflow was another major design concern. Supply air is strong enough to prevent
stratification or condensation from forming on the center’s wall of floor-to-ceiling panoramic view windows, but not strong
enough to unnecessarily increase pool surface evaporative rates or chill participants, according to Nerurkar. Additionally,
the natatorium’s opposite wall has interior windows allowing weight-room participants an excellent view through the
natatorium’s two exterior walls of windows. To assure these requirements, United’s air distribution uses a conventional
overhead perimeter aluminum duct system, but also an under deck duct system in a utility tunnel provided by the
architect’s design. While the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE),
recommends under deck air distribution for proper window coverage, many pool facilities omit it because of cost.
An underground tunnel that’s large enough to accommodate HVAC ductwork is an example of how important it is for
consulting engineers and architects to work in concert on projects, according to Giles. Fortunately, Corley Redfoot Zack
realized the value of such a space after having finished a natatorium with underground utility tunnels. “Winter outside
temperatures in the mountains can go as low as 10 or 15 degrees below 0° Fahrenheit, so it was important to keep the
windows evenly bathed in warm, dry air from above and below to eliminate condensation,” said Giles.
Associated Heating & Air Conditioning, North Wilkesboro, N.C., fabricated the under deck aluminum duct and installed it
along with the overhead aluminum perimeter spiral round duct system. Associated also installed the three Dectron
dehumidifiers. Two dehumidifiers—DSFA-242 models--are located in one mechanical room. The third unit, a remotely
located DA5-080 was added when the pool size increased during the planning stages without equal mechanical room
enlargement.
Other equipment in the project include Aerco International, Northvale, N.J., domestic hot water heat exchangers;
Armstrong International (CSP), Three Rivers, Mich., pumps; and a 300-ton chiller by Trane (CSP), Tyler, Texas.
The new recreation center has added a new twist to student social gatherings in the unique environment of an indoor
pool. “The air quality in the natatorium is very good,” said Joe Carter, director of university recreation. Page 2of 2